DN-6859:A • 10/10/06 — Page 3 of 4
Installation
Expansion modules mount to the back of the master modules
with the hardware provided.
The master module mounts in one module position of a CHS-
4N or CHS-M2 chassis using two captive screws. The
Expander Ribbon cable connects the module to the CPU mod-
ule.
The ARM-4 is mounted on the rear of the CHS-4N or CHS-MZ
chassis (adjacent to the controlling CRM-4RK/CRE-4), and
may be located under an ICM-4RK, or CRM-4RK (with or with-
out expanders).
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
• UL Listed: S635
• ULC Listed: CS118
• MEA Listed: 317-01-E(NFS-640, except IZM-8RK, IZE-A);
345-02-E (NFS-3030); 232-06-E (NFS2-3030)
• FM Approved: NFS-640 (except IZM-8RK, IZE-A);
NFS-3030
• California State Fire Marshall: 7165-0028:214 (NFS-640,
except IZM-8RK, IZE-A); 7170-0028:216 (NFS-640, except
VCM-4RK, IZM-8RK, IZE-A); 7165-0028:223 (NFS-3030,
NFS2-3030); 7170-0028:228 (NFS-3030, NFS2-3030)
• U.S. Coast Guard: 161-002/42/41 (except IZE-A, VCM-
4RK, VCE-4, DCM-4RK)
• Lloyd’s Register: 02/60007 (except ICE-4, CRE-4, VCE-4,
ARM-4, IZE-A)
• China Classification Society (CCS): NL05T00001
• Fire Service Department (Hong Kong)
• City of Chicago approved: Class1, Class 2
• City of Denver approved
Specifications
Temperature and humidity ranges: This system meets
NFPA requirements for operation at 0°C to 49°C (32°F to
120°F); and at a relative humidity (noncondensing) of 85% at
30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C (89.6°F ±
1.1°F) per ULC. However, the useful life of the system’s
standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humid-
ity. Therefore, it is recommended that this system and all
peripherals be installed in an environment with a nominal room
temperature of 15°C to 27°C (60°F to 80°F)
FOR CRM-4RK, CRE-4, AND ARM-4:
• Programmable for activation when an alarm is detected for
an individual zone, a group of zones, or all zones.
• Form-C (SPDT) contacts UL rated at 5 amps @ 30 VDC or
125 VAC (resistive); and 2 amps @ 125 VAC (inductive)
[CRM-4RK and CRE-4 modules].
• Form-C (SPDT) contacts rated at 20 amps @ 30 VDC or
125 VAC or 250 VAC (normally open contacts) or 10 amps
@ 30 VDC or 125 VAC or 250 VAC (normally closed con-
tacts) [ARM-4 module].
• Current draw: For CRM-4RK, 0.007 A in standby, 0.072 A
in alarm. For CRE-4, 0 A in standby, 0.065 A in alarm. For
ARM-4, 0 A in standby, 0.148 A in alarm.
Initiating Zone (IDC)
Module
(IZM-8RK)
Notification Appliance
Circuit Module (ICM-4RK)
Voice Control Module
(VCM-4RK)
Dual Channel Module
(DCM-4RK)